- For control of drives with a DC motor for DC 24 V
- Two relays per output for polarity switching of the output voltage
- Rated contact operating voltage DC 24 V
- Rated contact current: 6 A
- Electronics for detection of the actuation of an electromechanical and electronic limit switches
- Automatic travel time determination via current detection
- Per actuator channel direct operation function on the device for driving solar protection up/down, stop command and slat adjustment
- Two status LEDs per actuator channel to indicate the direction of travel and an override
- Button on the device front for deactivation of the direct mode operation and LED to indicate activation direct mode operation
- Maintenance-free terminals for connection and through-wiring of untreated single-core, stranded or multi-core conductors, 0.5 … 2.5 mm²
- Two terminals per actuator channel for motor connection (up, down)
- Two terminals on the device to connect the DC 24 V (+/-) to supply the load circuits
- Bus-powered electronics
- Housing: plastic, color RAL 7035 (light grey), N-system
- DIN rail mounted device for mounting on rail TH35 according to DIN EN 60715
- Type of protection: IP 20
Additional functionalities GAMMA
- Selectable operation mode blinds, shutter/awning, ventilation flap
- Per actuator channel motion commands for moving and stopping the solar protection or for adjustment of blind slats
- Per actuator channel direct movement to a position of the sunblind and the blind slats
- Per actuator channel central movement of the solar protection in manual mode and automatic mode and delay time for Up / Down
- Distinction between automatic and manual mode (position of the sunblind and blind slats) and adjustable behaviour in sunshine
- Programming and recalling preset positions 1-4 and 8-bit scene control
- Adjustable behaviour in case of override (wind, rain, frost, lock, forced position, forced control, range limitation)
- Adjustable reverse pause time and delay times of the drives
- Per actuator channel configurable state on bus voltage failure and start value on bus voltage recovery
- Adjustable transmission of status objects (direct operation, automatic operation, curtain and slat position, travel, calibration travel time to end positions, overriding) on request, cyclically and/or upon change
- Adjustable transmission time of the status objects after bus voltage recovery and transmission delay between the status objects
- Surveillance of device function