- Signal output humidity: DC 0...10 V
- Signal output temperature: DC 0...10 V
- Operating voltage: AC 19.2…28.8 V, 24 V, DC 13.5…35 V
- Measuring range, temperature: 0…50 °C, -35…35 °C, -40…70 °C
- Measurement range humidity: 0…100 % r.h.
- Measurement accuracy: At 15…35 °C: ±0.6 K, At 40…70 °C: ±0.8 K23 % r.h., 0…100 % r.h.: ±2 % r.h.±2 % r.h.
- Time constant: Humidity: 20 s, Temperature: 20 s, Air v=2 m/s: 210 s
- Immersion length: 90…206 mm
- Connection, electrical: Round connector
- Type of fixing: Flange
- Degree of protection: IP65
- Dimensions (W x H x D): 80 x 117 x 39 mm
- Warranty: 60 Months
Vui lòng để lại số điện thoại, chúng tôi sẽ gọi lại sau 5 phút